Loading...
Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0023-01 Batt.
overtem
p.
Minor Automa
tic
An alarm is generated, and
the battery lifespan is
aected.
Possible causes:
The ambient
temperature of
batteries exceeds the
battery high
temperature alarm
threshold (default
value: 50°C).
The battery charge/
discharge current
exceeds the upper
threshold.
Measures:
Install more cooling
equipment such as
air conditioners.
Control the battery
charge/discharge
current by reducing
loads.
0025-01
Batt.
overvolt
.
Minor Automa
tic
An alarm is generated, and
the battery lifespan is
aected.
Possible causes:
The congured
number of batteries
is less than the
actual number.
The battery string
charge voltage
exceeds the upper
threshold.
Measures:
Check battery
parameter settings.
Disconnected the
external battery
charger, check
whether the alarm is
cleared. If not,
contact Huawei
technical support for
repair.