Item Description Def
aul
t
Val
ue
Value
Range
Time
interval
Set the time interval for shallow discharge
tests. The parameter is congurable in any
mode.
60
day
s
30–90
days
Discharge
ratio
Set the proportion of the discharge capacity
to the total discharge capacity. The
parameter is congurable in any mode.
20
%
10%–
50%
4.6.3.5 Restoring Factory Settings
You can restore factory settings after the inverter shuts down.
4.6.4 Control Screen
On the Main Menu screen, select Control, and press . The Control screen is
displayed.
Startup Menu
The Startup menu allows you to restart the inverter.
Figure 4-44 Startup screen
Shutdown Menu
The Shutdown menu allows you to shut down the inverter.
Figure 4-45 Shutdown screen
Replace Batteries Menu
If the batteries have been replaced for the system, set this parameter. The
parameter is
congurable in non-battery mode or non-battery ECO mode.
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 82