EasyManua.ls Logo

Huawei UPS2000 - Page 36

Huawei UPS2000
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS2000-(6 kVA-20 kVA)
Modbus Protocol Development Guide
2 Modbus Card Signal List
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Alarm
ID
Alarm
Cause
ID
Alarm
Basic
Register
Address
Bit
Value
0024
1
Battery undertemperature
40163
2
0025
1
Battery overvoltage
40163
3
0027
1
Battery overcurrent
40164
0
0029
1
Maintain battery
40164
1
0036
1
Battery maintenance notification
40164
2
0026
1
Battery undervoltage
40164
3
0086
1
Bypass transfer overlimit
40165
2
0012
1
Bypass neutral loss
40165
6
0096
1
Abnormal ECO voltage
40165
13
0028
1
Breaker OFF
40168
0
0028
2
Breaker OFF
40168
1
0028
3
Breaker OFF
40168
2
0105
5
Communication failure
40168
3
0125
1
Inconsistent parallel parameters
40168
4
61440
1
Flash fault
40168
5
0040
1
Rectifier fault
40169
0
0040
2
Rectifier fault
40169
1
0040
4
Rectifier fault
40169
3
0040
5
Rectifier fault
40169
4
0040
6
Rectifier fault
40169
5
0040
7
Rectifier fault
40169
6
0040
9
Rectifier fault
40169
8
0040
10
Rectifier fault
40169
9
0042
1
Internal fault
40169
13
0042
2
Internal fault
40169
14
0044
1
Incompatible version
40169
15
0044
2
Incompatible version
40170
0
0044
3
Incompatible version
40170
1
0020
1
Battery reverse
40170
2

Related product manuals