32 ElEctrIcal / rEfrIgEratIon / controllEr
Hussmann Controller Operation RTN
The Controller controls refrigeration temperature. This is factory installed in the control panel. Defrosts
are time initiated and temperature terminated for self contained. The defrost setting is factory set
as shown above. To ensure a thorough defrost, defrost must be terminated by the temperature
termination setting — not by time.
The graph shows what the discharge air sensor is reading. The case controller is
pre-programmed from the factory with a set point of -8° F. This merchandiser
holds product in all locations between 7° F and -6° F (evaluated under ASHRAE
72 method).
GDF 3.0 SHEET SIZE D
NOTES:
1. APPLICABLE STANDARDS / SPECIFICATIONS
ASME Y14.5M-1994, DIMENSIONS AND TOLERANCES
2. KEY PRODUCT CHARACTERISTICS PER EPR-0006 & IDENTIFIED WITH SYMBOL
3. MATERIAL-
4. REF -
K
SHEET 3 OF 12
P/N
REV
THIRD
ANGLE
PROJECTION
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES.
R
LOAD LIMIT LINE
SECTION A-A
A
A
54.75
Model Product Application
Discharge Air Temperature
( Refrigeration Mode )
Controller Set Point
Range ( ° F )
Defrost Frequency
( per day )
Type of Defrost
Temp.
Termination
Failsafe
time ( min )
VRL1B1A Frozen Food - DOE -10 to 0 ° F (-23 to -17 ° C )
*** -10 to -8 ° F ( - 23 to - 22 ° C ) 3 Hotgas 55 ° F ( 12 ° C ) 50
VRL2B1A Frozen Food - DOE
-7 to 2 ° F (-21 to -16 ° C ) *** -10 to -8 ° F ( - 23 to - 22 ° C ) 3 Hotgas 47 ° F ( 8 ° C ) 40
-10
-5
0
5
10
15
20
25
30
VRL1B1A - Discharge Air Temp Sensor ( ° F ) @ 75 °F 55 % RH ( DOE )
Notes *** :
1) Controller Set point from factory is - 8 °F for VRL1B1A
2) Controller Set point from factory is - 10 °F for VRL2B1A.
3) The controller set poing range listed in the table above may be required when you are evaluated the product under ASHRAE 72 - FF DOE conditions to achieve IAT 0 °F.
Model Product Application
Discharge Air Temperature
( Refrigeration Mode )
Controller Set Point
Range ( ° F )
Defrost Frequency
( per day )
Type of
Defrost
Temp.
Termination
Failsafe
Time ( min )
VRL1B1A Frozen Food - DOE 0 *** -10 to -8 ° F ( - 23 to - 22 ° C ) 3 Hotgas 55 ° F ( 12 ° C ) 50
VRL2B1A Frozen Food - DOE ´-7 to 2 ° F (-21 to -16 ° C ) *** -10 to -8 ° F ( - 23 to - 22 ° C ) 3 Hotgas 47 ° F ( 8 ° C ) 40
VRL3B1A Frozen Food - DOE ´-7 to 2 ° F (-21 to -16 ° C ) *** -10 to -8 ° F ( - 23 to - 22 ° C ) 3 Hotgas 60 ° F ( 15 ° C ) 40
Notes *** :
1) Controller Set point from factory is - 8 °F for VRL1B1A
2) Controller Set point from factory is - 10 °F for VRL2B1A.
3) Controller Set point from factory is - 10 °F for VRL3B1A.
4) The controller set poing range listed in the table above may be required when you are evaluated the product under ASHRAE 72 - FF DOE conditions to