6 Error Message
6 - 5
Error Code Details Causes
The size of the burn-in program exceeds the limit
H4 Series:56k
H6 Standard: 56k= 896 lines, 64bytes per line
H6 Turning/Milling: 56k +128k (saving capacity for
function key) =2944 lines. Since the current limit for burn-
in is 128k, therefore the maximum size is 128k (=2048
lines).
N
The declared command exceeds 20 program lines (G11,
G12, G04, M-code).
L
L error in G10 P0920 Lxxxx
(L shall not be empty, and 0<=LA<1000)
12
P
Program specified by Lxxxx in G10 P0921 Lxxxx has
not been declared.
Message
The capacity of the replicating program is too big (exceeding 128KB).
Remedy:
1. Check the program for incorrect writing.
2. Check the capacity for the program.
Error Code Details Causes
G
G error code.
During the G87 command, neither of R209 BIT10 and 11
is ON.
T T error code.
M M error code (MA<0).
13
R
An R error in commands G81~G89.
(1) R and Z(A) have different symbols.
(2) R and [Z(A)-R] have different symbols.
Message
The program information contains the R Error of G-Code, M-Code or G81-G89 that
are not being set by H6D-T Series, and they cannot be accepted by the Controller.
Remedy:
Check the program and check if the R setting of G-Code, M-Code or G81-G89 is
correct.