8
User Manual | Temperature Controller Display HIB123 Part-No.: 3756766 Doc.-Version: I
e) Parameter group OPH (Operating hours)
The parameter group OPH shows the operating hours of each component (actuators).
Example: 0_H = 1 0_L = 85 Operating time of the compressor is 1085 hours (1 * 1000 + 85).
Parameter
Component / Actuator
Multiplication factor


Compressor
(at multi-compressor systems: Compressor 1)
1
1000


Pump
1
1000


Heating
1
1000


HGB-Valve
(at multi-compressor systems: Compressor 2)
1
1000


Fan or DI-Valve
(at multi-compressor systems ≥ 3 compressors: Compressor 3)
1
1000


DI-Valve
(at multi-compressor systems ≥ 4 compressors: Compressor 4)
1
1000


No parameter assigned
(for compressor with systems ≥ 5 compressors: compressor 5)
1
1000


No parameter assigned
(for compressor with systems ≥ 6 compressors: compressor 6)
1
1000
Notice:
/ For conductance control, the operating hours counter refers to the DI valve.
In this case the operating hours of the fan correspond to the running time of the compressor (/ )