User Guide Oxymatic Basic
Rev.Apr 2013
Hydrover Water Solutions S..L.U.
17
Programming table minutes for each hour of operation
8. Once the programming is completed, reset the screws from the top of the team. Using the 4 screws.
9. Connect the power BASIC Oxymatic 110-220
10. Press the MODE
11. Place the FLOW-based computer and work computer BASIC Oxymatic automatically.
b) pH Programming: To program the values of the pH set points, follow these steps.
NOTE: Your computer is already programmed with the set points with the following information.
This means that when the pH is below 7.0, the pump does not inject the liquid pH lowering pH.
This means that when the pH is above 7.8, pH pump is working at 100% of its maximum power.
Set the Set Points 1: OFF
1. Press the MODE key.
2. Put the computer in the manual position.
3. Press the "Sol 1" light is on.
4. Then press the "OK" in light of the position set point will turn off lights with "Sol 1" "SUN 2".
5. Then press the "Sol 1" to lower the set point off or press the "SUN 2" to raise the set point OFF then select
the desired set point.
6. Press OK to save the information.
Set the Set Points 100%
1. Press the MODE key.
2. Put the computer in the manual position.
3. Press the "SOL 2" light comes on.
4. Press the "OK" in light of the position set point 100% will turn next to the "SOL1" and "SOL 2".
5. Press the "Sol 1" to lower the set point 100%, or press the "SOL 2" to increase 100% set point, then select
the desired set point
6. Press the "OK" to save the information.
Calibration of the pH probe:
1. Press the MODE key.
2. Put the computer in the manual position.
3. Press the "CAL" and then "OK" to confirm
4. Enter the pH 7.0 buffer in the
5. Press the "SOL 1" to start reading the buffer 7.0, the LED "Sol 1" will light intermittently.
6. The team will give an audible signal to indicate the end of the calibration and the LED "SOL 2" lights.
7. Removing the electrode from 7.0 buffer and wash with clean well water, once in place it Limpi 9.0 buffer
solution.
8. Press the "SOL 2" to start reading the 9.0 buffer, the LED "SOL 2" will blink.
9. The team will give an audible signal to indicate the end of the calibration and the LED "SOL 2" lights.
10. THE BASIC Oxymatic will give two beeps and lights up for a moment the LED "OK"
11. After this operation, the calibration is completed correctly and the machine will "MAN" position
automatically.
PIND
MINUTES X
4 5
6
HOUR
- - -
0 minutes
- - ON
1 minute
- ON
-
2 minutes
- ON
ON
3 minutes
ON - -
6 minutes
ON - ON
12 minutes
ON ON
-
15 minutes
ON ON
ON
20 minutes
Set point 1:
OFF
=7.0
Set point 2:100%
=7.8