14. Turn on the gas supply shut off valve, and soap test for leaks.
Fuel High fire Low fire
CO max
PPM
Range % Target %
Range % Target %
Natural Gas
9.0 - 10.0 9.5
8.2 - 9.2 8.7
<150
Propane
10.3 - 11.3 10.8
9.3 -10.3 9.8
< 250
Table 11 Combustion test target ranges - CO
2
/ Maximum CO
Note: Low Fire CO
2
should be at least 0.5% lower than High Fire CO
2
73
6.3.3 Adjusting the gas valve

Table of Contents