IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x 7
Table 6. IBM 3000VA UPS (230V) runtime chart
Load Run time on batteries
Percent Load VA Watts Run time with standard internal
battery only
Run time with internal battery plus
External Battery Module (EBM)
25% 710 670 41 minutes 156 minutes
50% 1450 1350 17 minutes 81 minutes
75% 2160 2020 10 minutes 41 minutes
100% 2880 2680 7 minutes 27 minutes
Note: Battery backup times are approximate and may vary with equipment, configuration, battery age,
and temperature.
Physical specifications
Here are the physical specifications of the 3U uninterruptible power supply:
Height: 127 mm (5.0 in)
Width: 438 mm (17.2 in)
Depth: 527 mm (20.8 in)
Weight: 53953AX - 38.5 kg (84.8 lb) / 53953JX - 39.2 kg (86.4 lb) / 53953KX - 40.9 kg (90.1 lb)
Here are the physical specifications of the 3U Extended Battery Module:
Height: 127 mm (5.0 in)
Width: 438 mm (17.2 in)
Depth: 527 mm (20.8 in)
Weight: 119 lb
Operating environment
The IBM 3000VA LCD 3U Rack UPS is supported in the following environment:
Temperature:
Operation: 0 to 40 °C (32 to 104 °F)
Storage: -15° to 30° C (5° to 86° F) - charge the UPS battery every six months
Storage: 30° to 45° C (86° to 113° F) - charge the UPS battery every three months
Relative humidity: 5 to 95%
Maximum altitude:
Operation: 3,000 m (10,000 ft)
Storage: 15,000 m (50,000 ft)
Warranty
The IBM 3000VA LCD 3U Rack UPS has a three-year limited warranty.