2. Set the GlobalDelayTimer parameter with the object identier (OID) as shown in the following
illustration.
3. Set the IndividualDelayTimer parameter with the OID.
Using Telnet through the Ethernet port
Set the parameters for the power-on sequence function by using an Ethernet port and the Telnet
interface.
About this task
To set the parameters for the power-on sequence function by using an Ethernet port and the Telnet
interface, complete the following steps:
Procedure
1. Log in as ADMIN/1001.
2. Type 1 for System Conguration.
3. Type 3 for Outlet Global Delay Timer and PDU Location.
4. Type 15 to dene the Outlet Global Delay Timer.
5. Type the value for the New Outlet Global Delay Timer.
6. Type 0 to return to the previous menu.
7. Type 4 for the Outlet Name and Individual Delay Timer.
8. Type the outlet number and enter the outlet name and its IndividualDelayTimer value.
Using HyperTerminal through the serial port
Set the parameters for the power-on sequence function by using a serial port (HyperTerminal interface).
About this task
To set the parameters for the power-on sequence function by using a serial port (HyperTerminal
interface), complete the following steps:
Procedure
1. Make sure that the serial port conguration is 115200, 8-N-1-None.
2. Log-in as ADMIN/1001.
3. On the IBM PDU Conguration Utility main meu, type 8 to select Set PDU Location and Outlet
Information.
4. Ttype the GlobalDelayTimer value.
5. On the main menu, type the IndividualDelayTimer values for each outlet.
Using the web interface
Use the web interface to congure and monitor the PDU remotely. The PDU provides a graphical user
interface that you can view from a web browser. Using a web browser, you can access and monitor the
PDU power outlets and output devices remotely from a workstation or notebook computer.
Starting the web interface
To start the web interface, complete the following steps.
Procedure
1. Start a web browser from a workstation or notebook computer and enter the IP address of the PDU in
the address eld. The Login window opens.
2. In the User Name eld, type ADMIN (all uppercase letters). In the Password eld, type 1001.
3. Click Login. The main status page opens.
The main status page shows the PDU power outlets and input status per load segment: