Specifications
Dimensions
Height: 1577 mm (62.0 inches)
Depth: 1019 mm (40.1 inches)
Depth (without doors): 887 mm (34.9 inches)
Width: 650 mm (25.5 inches)
Weight
Empty Rack: 158 kg (349 pounds)
Standard Configuration: 205 kg (450 pounds)
Maximum Configuration: 455 kg (1000 pounds)
Power
-48 V DC Model S00
Standard Configuration: 1.5 kVA
Maximum Configuration: 2.0 kVA
AC Model S00
Standard Configuration: 0.6 kVA
Maximum Configuration: 2.2 kVA
System Limit: 4.8 kVA
Operating Voltage: 200 to 240 V AC
Frequency: 50 or 60 Hz
Temperature Requirements
Operating: 10 to 405C (50 to 1045F)
Nonoperating: 10 to 525C (50 to 1265F)
Relative Humidity Requirements (Noncondensing)
8 to 80%