External AC Power Cables
To avoid electrical shock, the manufacturer provides a power cable with a grounded
attachment plug. Use only properly grounded outlets.
Power cables used in the United States and Canada are listed by Underwriter's
Laboratories (UL) and certified by the Canadian Standards Association (CSA).
These power cords consist of the following:
Electrical cables, type ST
Attachment plugs complying with National Electrical Manufacturers Association
(NEMA) L6-30P
Appliance couplers complying with International Electrotechnical Commission
(IEC) Standard 320, Sheets C13 and C14.
Power cables used in other countries consist of the following:
Electrical cables, type HD21 or HD22
Attachment plugs approved by the appropriate testing organization for the
specific countries where they are used
Appliance couplers complying with International Electrotechnical Commission
(IEC) Standard 320, Sheet C13 and C14.
Refer to “Detail 11. Power Cords” on page 6-22 of Chapter 6, Parts Information (AC
Rack) to find the power cables that are available for the AC Model S00 rack.
-48 V DC Power Cables
e customer is responsible for providing power cables from the customer's power
source to the power distribution panel (PDP). The -48 V DC Model S00 rack must
be connected to a -48 V DC power source which is electrically isolated from its AC
power source. In addition, the -48 V DC source is to be reliably grounded.
Note: The -48 V DC Model S00 rack may be connected to two separate -48 V DC
power sources. Both power sources must be properly isolated and grounded.
Power cables used in the United States and Canada are listed by Underwriter's
Laboratories (UL) and certified by the Canadian Standards Association (CSA).
These power cables have the following characteristics:
Power cables and ground cables must be a minimum of 6 AWG stranded copper
(or equivalent) for lengths up to 50 feet from the power source.
All connectors must be the copper crimp type (compression). Connector metal
must be compatible with the cable metal.
1-20 7014 Model S00 Rack Installation and Service Guide