Table 3-1 (Page 19 of 26). Firmware Error Codes.
Error Code Description Action / Possible Failing FRU
2BA00367 Service Processor reports Locked
DASD Fan #4.
1. Remove Obstruction from DASD
Fan 4.
2. Replace DASD Fan 4.
3. If problem persists, replace Power
Supply.
4. Replace I/O Board. (See notes on
3-1.)
2BA00368 Service Processor reports Slow CEC
Fan #1.
1. Replace CEC Fan 1.
2. If problem persists, replace Power
Supply.
3. Replace I/O Board. (See notes on
3-1.)
2BA00369 Service Processor reports Slow CEC
Fan #2.
1. Replace CEC Fan 2.
2. If problem persists, replace Power
Supply.
3. Replace I/O Board. (See notes on
3-1.)
2BA00370 Service Processor reports Slow CEC
Fan #3.
1. Replace CEC Fan 3.
2. If problem persists, replace Power
Supply.
3. Replace I/O Board. (See notes on
3-1.)
2BA00371 Service Processor reports Locked CEC
Fan #1.
1. Remove Obstruction from CEC Fan
1.
2. Replace CEC Fan 1.
3. If problem persists, replace Power
Supply.
4. Replace I/O Board. (See notes on
3-1.)
2BA00372 Service Processor reports Locked CEC
Fan #2.
1. Remove Obstruction from CEC Fan
2.
2. Replace CEC Fan 2.
3. If problem persists, replace Power
Supply.
4. Replace I/O Board. (See notes on
3-1.)
2BA00373 Service Processor reports Locked CEC
Fan #3.
1. Remove Obstruction from CEC Fan
3.
2. Replace CEC Fan 3.
3. If problem persists, replace Power
Supply.
4. Replace I/O Board. (See notes on
3-1.)
2BA00374 Service Processor reports Power
Supply #1 and DASD Fans failed.
1. Replace Power Supply #1 and
Failing DASD Fans.
2. Replace I/O Board (See notes on
3-1.)
3-20 RS/6000 Enterprise Server Model H50 Installation and Service Guide