IBM System x3650 M4 52
Physical and electrical specifications
Dimensions and weight:
Height: 86.5 mm (3.4 in)
Width: 445 mm (17.5 in)
Depth: 746 mm (29.4 in)
Weight:
Minimum configuration: 25 kg (55 lb)
Maximum configuration: 30 kg (65 lb)
Supported environment:
Air temperature:
Server on: 5 °C to 40 °C (41 °F to 104 °F); altitude: 0 to 950 m (3,117 ft); decrease the maximum
system temperature by 1 °C for every 175-m increase in altitude.
Server off: 5 °C to 45 °C (41 °F to 113 °F)
Maximum altitude: 3,050 m (10,000 ft), 5 °C to 28 °C (41 °F to 82 °F)
Shipment: -40 °C to +60 °C (-40 °F to 140 °F)
Humidity:
Server on: 8% to 85%, maximum dew point 24 °C, maximum rate of change 5 °C/hr
Server off: 8% to 85%, maximum dew point 27 °C
Design to ASHRAE Class A3, ambient of 36 °C to 40 °C (96.8 °F to 104 °F), with relaxed support:
Supports cloud like workload with no performance degradation acceptable (Turbo-Off).
Under no circumstance can any combination of worst case workload and configuration result in
system shutdown or design exposure at 40 °C.
The worst-case workload (like Linpack, Turbo-On) might have performance degradation.
Electrical:
Models with 900 W power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 10 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 5 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.15 kVA
Maximum configuration: 1.02 kVA
Models with 750 W ac power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 8.9 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.5 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.15 kVA
Maximum configuration: 0.9 kVA
Models with 550 W power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 6.5 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 3.3 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.16 kVA
Maximum configuration: 0.66 kVA

Other manuals for IBM System x3650 M4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM System x3650 M4 and is the answer not in the manual?

IBM System x3650 M4 Specifications

General IconGeneral
Form Factor2U Rack
Memory Slots24 DIMM slots
ProcessorIntel Xeon E5-2600 series
MemoryUp to 768GB DDR3
StorageUp to 16 x 2.5-inch or 6 x 3.5" hot-swap SAS/SATA HDDs or SSDs
Power SupplyRedundant hot-swap 550W, 750W, or 900W
Network InterfaceQuad-port 1 GbE
ChipsetIntel C600
RAID SupportRAID 0, 1, 10, 5, 6, 50, 60
Expansion SlotsUp to 6 PCIe slots
Operating System SupportWindows Server, Red Hat Enterprise Linux, SUSE Linux Enterprise Server, VMware

Related product manuals