EasyManua.ls Logo

IBM UPS3000 - IBM UPS3000 Base Model Specifications

IBM UPS3000
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IBM System x – UPS3000 Training
© 2003 IBM Corporation
28 October 2007
© 2007 IBM Corporation
IBM UPS3000 Base Model Specifications
Models (LV, HV) 21301RX, 21302RX, 21301JX, 21302JX, 40K9620, 40K9788
VA Rating 3000VA @ 200 – 208V, 2880VA @ 110 - 127V, 2400VA @ 100V
Watts 2700Watts (0.95 power factor) 110V and above, 2250 Watts @ 100V
Form Factor 2U + tower to rack convertible
Outlets 9 IEC13 + 1 C19 (HV); 6 NEMA 5-15 + 1 PDU outlet (20 amp) NEMA L5-30
Outlet grouping/control 3 segments: 2 sets of outlets + the PDU outlet
Line cord LV unit- fixed: HV: C19/20 input to country cord (30 amp input)
Communication ports Serial + Network Card
Battery backup times 5 minutes at full load/ 15 minutes at half load on UPS
Able to add battery packs YES up to 4 (limited by weight)
Run time with battery packs 1 unit 25 minutes
2 units 49 minutes
3 units 69 minutes
4 units 90 minutes
IBM Director Integrated? Standard
Software Included Full suite of easy to use management software- LanSafe for IBM
OS Support Windows, Linux RedHat 7.2, and NetWare 6.0
Warranty 3 year parts and labor

Related product manuals