MICROmatic MINImatic MIDImatic - MULTImatic
Sistemi di rifasamento automatici
Manuale operativo di installazione, uso e manutenzione
Automatic power factor correction systems
Installation, operating and maintenance instruction manual
Systèmes de compensation de l’énergie réactive
Manuel opératif d’installation, utilisation et entretien
MAT 189 revJ Jan2018

Questions and Answers

  • C
    Cole Osborn DDSAug 9, 2025
    Why won't the capacitor banks switch in on my Icar Portable Generator?
    • M
      marywilsonAug 9, 2025
      If the Icar Portable Generator's controller doesn't switch in the capacitor banks, ensure the current transformer is correctly positioned upstream of all loads and power factor correction. Also, verify that the current transformer is enabled on phase L1 (R) and that the controller is not set to manual mode. If the amperage of the current transformer is lower than the sensitivity threshold, increase the load current or use a current transformer with an adequate primary ratio.
  • J
    Jennifer WarrenAug 15, 2025
    Why does my Icar MINImatic controller show an unreal power factor?
    • C
      chris26Aug 15, 2025
      If your Icar Portable Generator controller displays an unreal power factor, the current transformer may be enabled on the incorrect phase. Ensure it is positioned on phase L1 (R) as referred to in our cabinet. If the issue persists, the current transformer itself may be faulty and require replacement with a suitable one.
  • M
    markroyAug 20, 2025
    What to do if my Icar MINImatic switches in all capacitor banks but the power factor doesn't increase?
    • S
      Samantha GarciaAug 21, 2025
      If the Icar Portable Generator controller switches in all the capacitor banks without increasing the power factor on the display, it might be due to the current transformer being installed at an incorrect point. Ensure it's positioned upstream of all the loads and power factor correction system. Also, check that the current transformer is enabled on phase L1 (R) as referred to in our cabinet.
  • D
    Danielle PerezAug 27, 2025
    How to fix an Icar MINImatic Portable Generator controller that won't switch on?
    • A
      Ashley FlemingAug 27, 2025
      If the Icar Portable Generator controller fails to switch on, first ensure the disconnect switch is turned on. If it still doesn't power up, check for blown control circuit fuses and replace them after identifying the cause. Also, verify that the quick connect terminal boards inside the unit are correctly engaged. If these steps don't resolve the issue, check the controller's power supplies; if they are regular, replace the controller with one of the original type.
  • D
    dscottSep 2, 2025
    What to do if Icar MINImatic Portable Generator controller switches capacitor banks in and out without balance?
    • L
      lthompsonSep 2, 2025
      If the Icar Portable Generator controller switches the capacitor banks in and out continually without finding a balance, it is likely due to a faulty setting of the controller parameters. Check the current parameters and set them correctly.

Summary

Preliminary Operations

General

Environmental Conditions

Connection to Main Power Supply

Location

Reactive Power Controller

Start-Up and Operation

Trouble Shooting During Installation

Maintenance

Routine Maintenance

Outlines periodic checks and cleaning tasks for system upkeep.

Safety Recommendations

Precautions Regarding Use

Information and Technical Service

Annex B: Connection Diagrams

Annex C: Component Locations

Annex D: Installation Dimensions

Annex E: Cable Cross-Sections

Maintenance Record