5. Staged Off Outputs
Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously.
1 = outputs staged off independently
0 = outputs off simultaneously (best for dual fuel)
Note: For 2 compressor heat pumps and multi-stage gas/oil systems,
stage 3 is staged off independently when SO is set to O.
Press the up or down button to set.
Press the right button to advance to the next screen.
6. Minimum Deadband (1°F to 9°F) (1°C to 5°C)
Set the minimum separation between heat setpoint and cool setpoint in
Auto Changeover Mode.
Press the up or down button to set deadband value.
Press the right button to advance to the next screen.