14
9. Outdoor Upper Setpoint (50°F to 25°F, – –) (10°C to -4.0°C, – –)
Appears only if heat pump is selected.
Note:
See chart on Page 15 for more information
For Heat Pumps With Gas/Oil Backup
When the ambient temperature is below the selected temperature, the heat
pump will be locked out and only the furnace will operate.
For Heat Pumps With Electric Backup
When the ambient temperature is above the selected temperature, the heat
pump will operate and electric backup will be locked out.
Press the up or down button to select temperature.
Press the right button to advance to the next screen.
10. Outdoor Lower Setpoint (select – – to disable)
Appears only for heat pump with electric backup with outdoor upper
setpoint enabled.
Note:
See chart on Page 15 for more information
When the ambient temperature is below the selected temperature, heat
pump is locked out and only electric heat will operate
Press the up or down button to select temperature.
Press the right button to advance to the next screen.
See “Remote Sensor When Used as Outdoor Sensor” diagram on next page.