5. Soft Dry Operation Mode
During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 2°F, the compres-
sor OFF temperature is the setting temperature minus 1°F.
When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
Cooling operation.
When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
The operation diagram is shown below.
- 17 -
INTAKE AIR TEMP.
SETTING TEMP.
+
2
°
F
(Compressor ON)
SETTING TEMP. -1
°
F
(Compressor OFF)
Selecting
fan speed
Selecting
fan speed
Cooling
Operation
Soft Dry Operation
maximum
4 minutes
maximum
10 minutes
3 minutes
10 minutes
maximum
7 minutes
3 minutes
Cooling
Operation
COMPRESSOR ON OFF ON OFF ON OFF ON
INDOOR FAN SPEED Low Low Low Low Low