HR6S-BAC Safety Module
Safety-Related Outputs
Number of relay contacts, Normally Open 4
Number of relay contacts, Normally Closed 1
Maximum short circuit current IK 1 kA
Maximum continuous current, Normally Open relay contacts
6 A
Maximum continuous current, Normally Closed relay contacts
3 A
Maximum total thermal current ∑I
THERM
16 A
Minimum current 10 mA
Utilization category as per UL 60947-5-1
B300 and R300 for Normally
Open contacts
D300 and R300 for Normally
Closed contacts
Utilization category as per IEC 60947-4-1 and IEC 60947-5-1
AC-1: 250 V
AC-15: 250 V
DC-1: 24 V
DC-13: 24 V
Maximum current, normally open relay contacts
AC-1: 5 A
AC-15: 3 A
DC-1: 5 A
DC-13: 3 A
Maximum current, normally closed relay contacts
AC-1: 3 A
AC-15: 1 A
DC-1: 3 A
DC-13: 1 A
External fusing
10 A, category gG, for Normally Open
4 A, category gG, for Normally Closed
Data Functional Safety
Dened safe state
Safety-related outputs are de-energized
Normally Open: open
Normally Closed: closed
Maximum Performance Level (PL), Category
(as per ISO 13849-1:2015)
Normally Open: PLe, Category 3
Normally Closed: PLc, Category 1
Maximum Safety Integrity Level (SIL)
(as per IEC 61508-1:2010)
Normally Open: 3
Normally Closed: 1
Safety Integrity Level Claim Limit (SILCL)
(as per IEC 62061:2005+AMD1:2012+
AMD2:2015)
Normally Open: 3
Normally Closed: 1
Type (as per IEC 61508-2) B
Hardware Fault Tolerance (HFT)
(as per IEC 61508 and IEC 62061)
1
Stop Category for Emergency Stops
(as per ISO 13850 and IEC 60204-1)
0
Lifetime in years at an ambient temperature of 55 °C (131 °F)
20
Safe Failure Fraction (SFF)
(as per IEC 61508 and IEC 62061)
>99 %
Probability of Dangerous Failure per hour (PFH
D
) in 1/h
(as per IEC 61508 and ISO 13849-1)
0.95 × 10
-9
Mean Time To Dangerous Failure (MTTF
D
) in years
(as per ISO 13849-1)
2,300 (*1)
Average Diagnostic Coverage (DC
avg
)
(as per ISO 13849-1)
≥99 %
Maximum number of cycles
over lifetime
DC-13
24V DC 1 A: 1200000
24V DC 3 A: 275000
AC-1 250V AC 4 A: 90000
AC-15
250V AC 1 A: 90000
250 VAC 5 A: 70000
*1) According to ISO 13849-1 Annex K
For other specifications (common to all models), see page 27.
Protects both the operator and the machine by immediately stopping
dangerous movements when instructed to stop by the operator or when a
failure in the safety circuit is detected.
Reduced wiring for safety input part.
Slim module available with 4NO1NC safety output.
Terminal Part No. Supply Voltage
Push-in terminal HR6S-BAC1C 24V AC/DC
Screw terminal HR6S-BAC1P 24V AC/DC
• One sealing strip (see page 28) is included with each product.
HR6S-BAC Package Quantity: 1
22.5mm-wide module with 4NO1NC output
• See website for details on approvals and standards.
S
a
f
e
t
y
A
p
p
r
o
v
e
d
H
R
6
S
*
-
1
4
3
5
.
I
M
.
1
3
5
0
0
5
/
2
0
TÜV NORD Systems
GmbH & Co.KG
Monitoring of Emergency
Stop circuits as per ISO
13850 and IEC 60204-1,
stop category 0
Monitoring of guards as
per ISO 14119/14120
with interlock switches
Overview of Application Functions