5.3.1. SETPOINT PROGRAMMING
o MANUAL MODE
To fix the set point in a MANUAL way, maintain pressed the key “SET” (the superior
display will show “- - -“ until it is heard a “beep”, then release the key. The first digit of the
red display will light. Maintaining the key “SET” pressed, fix the wanted value of hundreds.
Once fixed, release the “SET” key. Repeat this operation with the digits of tenths and
units.
o AUTOMATIC MODE
The AUTOMATIC MODE allows to fix quickly the ORP value (mV) currently present in the
water as the setpoint value. Maintain the key “SET” pressed (the displays will fade).
Lapsed some seconds, a “beep” will be heard (the corresponding to the MANUAL MODE
programming. DO NOT RELEASE AT THIS POINT). Maintain the key “SET” pressed until
listen a second “beep.” In that moment, release the key “SET” and the set point value will
be automatically fixed to the ORP value (mV) currently present in the water.
26