EasyManuals Logo

IEC CPY 06 User Manual

Default Icon
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
13
SECTIONTHREE–NormalOperation&PeriodicMaintenance,Cont'd.
Motor/Blower Assembly
Thetypeoffanoperationisdeterminedbythecontrol
componentsandtheirmethodofwiring.Thismayvary
fromunittounit.Refertothewiringdiagramthatis
attachedtoeachunitforthatunit’sindividualoperating
characteristics.
Allmotorshavepermanentlylubricatedbearings.Noeld
lubricationisrequired.
Shouldtheassemblyrequiremoreextensiveservice,the
motor/blowerassemblymayberemovedfromtheunit
tofacilitatesuchoperationsasmotororblowerwheel/
housingreplacement,etc.
Dirtanddustshouldnotbeallowedtoaccumulateonthe
blowerwheelorhousing.Thiscanresultinanunbalanced
blowerwheelconditionwhichcandamageablower
wheelormotor.Thewheelandhousingmaybecleaned
periodicallyusingavacuumcleanerandabrushtaking
carenottodislodgethefactorybalancingweightsonthe
blowerwheelblades.
Coil
Coilsmaybecleanedbyremovingthemotor/blower
assembliesandbrushingtheenteringairfacebetween
nswithastiffbrush.Brushingshouldbefollowedby
cleaningwithavacuumcleaner.Ifacompressedairsource
isavailable,thecoilmayalsobecleanedbyblowingair
throughthecoilnsfromtheleavingairface.Thisshould
againbefollowedbyvacuuming.Unitsprovidedwiththe
propertypeofairlters,replacedregularly,willrequire
lessfrequentcoilcleaning.
Electric Resistance Heater Assembly
Electricresistanceheaterstypicallyrequirenonormal
periodicmaintenancewhenunitairltersarechanged
properly.Theoperationandservicelifemaybeaffected
byotherconditionsandequipmentinthesystem.The
twomostimportantoperatingconditionsforanelectric
heaterareproperairowandpropersupplyvoltage.High
supplyvoltageand/orpoorlydistributedorinsufcientair
owovertheelementwillresultinelementoverheating.
Thisconditionmayresultintheheatercyclingonthehigh
limitthermalcutout.Sheathheatershaveautomaticreset
switchesonly.Open-stripheatershaveanautomaticreset
switchwithaback-up,high-limitthermalswitch.
Automaticresetswitchesareasthenameimplies,they
resetautomaticallyaftertheheaterhascooleddown.
High-limitthermalswitchesmustbereplacedoncethe
circuithasbeenbroken.Thehigh-limitthermalcutout
deviceisasafetydeviceonly,andisnotintendedfor
continuousoperation.Withproperunitapplicationand
operation,thehigh-limitthermalcutoutwillnotoperate.
Thisdeviceonlyoperateswhenaproblemexists,andANY
conditionthatcauseshigh-limitcutoutMUSTbecorrected
immediately.Highsupplyvoltagealsocausesexcessive
amperagedrawandmaytripthecircuitbreakerorblow
thefusesontheincomingpowersupply.
Afterproperairowandsupplypowerareassured,
regularltermaintenanceisimportanttoprovideclean
airovertheheater.Dirtthatisallowedtodepositonthe
heatingelementwillcausehotspotsandeventualelement
burnthrough.Thesehotspotswillnormallynotbeenough
totripthehigh-limitthermalcut-outdevice,andmaynot
beevidentuntilactualheaterelementfailure.
Electrical Wiring and Controls
Theelectricaloperationofeachunitisdeterminedbythe
componentsandwiringoftheunit.Thismayvaryfrom
unittounit.Consultthewiringdiagramattachedtothe
unitfortheactualtypeandnumberofcontrolsprovided
oneachunit.
Theintegrityofallelectricalconnectionsshouldbe
veriedatleasttwiceduringtherstyearofoperation.
Afterwards,allcontrolsshouldbeinspectedregularly
forproperoperation.Somecomponentsmayexperience
erraticoperationorfailureduetoage.Wallthermostats
mayalsobecomecloggedwithdustandlint,andshould
beperiodicallyinspectedandcleanedtoprovidereliable
operation.
Whenreplacinganycomponentssuchasfuses,
contactors,orrelays,useonlytheexacttype,sizeand
voltagecomponentasfurnishedfromthefactory.Any
deviationwithoutfactoryauthorizationcouldresultin
personnelinjuryordamagetotheunit.Thiswillalso

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IEC CPY 06 and is the answer not in the manual?

IEC CPY 06 Specifications

General IconGeneral
BrandIEC
ModelCPY 06
CategoryAir Conditioner
LanguageEnglish

Related product manuals