3 Installation
Using process adapters the unit can be adapted to different process connections�
• Adapters have to be ordered separately as accessories�
A correct fit of the unit and ingress resistance of the connection are only
ensured using ifm adapters�
• For small flow rates ifm adapter blocks are available�
3.1 Installation location
General
•The sensor tip is to be completely sur-
rounded by the medium�
•Insertiondepthofthesensor:minimum
12 mm�
Recommended
•Forhorizontalpipes:mountingfrom
the side�
•Forverticalpipes:mountingintherising
pipe�
Conditional
•Horizontal pipe /mounting from the bot-
tom:ifthepipeisfreefrombuild-up.
•Horizontal pipe /mounting from the
top:ifthepipeiscompletelyfilledwith
medium�
To avoid
•The sensor tip must not be in contact
with the pipe wall�
•Donotmountindownpipesthatare
open at the bottom!