IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
70
>
9.3.7 Write output data of individual IO-Link ports
34452
Register area for separate access to output data of individual IO-Link ports: →Single Port Access
(→ S. 98)
The area contains the following data for each IO-Link port X01...X04:
Digital output data at pin 4 (DO)
IO-Link output data
► Observe the general rules for access to the Modbus registers (→Rules for accessing the
Modbus registers (→ S. 73))!
If the user tries to write more than 34 bytes of output data to a single port, the IO-Link master
cancels the execution of the command and returns the error code "2 ILLIGEAL ADDRESS".
► When writing outputs, ensure that the length of the transferred output data corresponds
with the configured process data length.
The output data is invalid in the following situations:
No Ethernet cable connected
PLC has terminated the connection
Connection to the PLC has a timeout
Register
Contents
Access
1100
Port X01: Digital Output - Pin 4 (DO)
r/w
1101
Port X01: Output Data IO-Link (n bytes)
r/w
2100
Port X02: Digital Output - Pin 4 (DO)
r/w
2101
Port X02: Output Data IO-Link (n bytes)
r/w
3100
Port X03: Digital Output - Pin 4 (DO)
r/w
3101
Port X03: Output Data IO-Link (n bytes)
r/w
4100
Port X04: Digital Output - Pin 4 (DO)
r/w
4101
Port X04: Output Data IO-Link (n bytes)
r/w
r/w ... read and write
n = [2,4,8,16,32]; is determined by parameter [Process Data Length] (→Configuration Area (→ S. 88)