IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
71
>
9.3.8 Read diagnostic information and events
34439
Register area for the access to diagnostic information of the IO-Link ports X01…X04:→Diagnostic
data ( S. 90)
The area contains the following data:
Status/error flags for port configuration
Vendor ID / device ID of the connected IO-Link devices
Events and corresponding event codes
Observe the general rules for access to the Modbus registers (Rules for accessing the
Modbus registers ( S. 73))!
A maximum of 3 events per IO-Link port are displayed.
One-time events will be deleted after a minimum of 10 s (Event Single Shot).
Occurring events indicate the time of the error occurrence (event appears). If the error cause
disappears, this is indicated by a further event (event disappears). Both event types always
occur in pairs.
Register
Contents
Access
30
Port X01: Diagnostic Data
r
40
Port X02: Diagnostic Data
r
50
Port X03: Diagnostic Data
r
60
Port X04: Diagnostic Data
r
r = read only
Additional diagnostic and status details are provided in the following register areas:
"Input Data" area: Read input data of several IO-Link ports ( S. 67)
"Single Port Access" area: Read input data of several IO-Link ports ( S. 67)