IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
97
>
Mapping: Digital output data
34493
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
X04:
Pin 4
0X03:
Pin 4
X02:
Pin 4
X01:
Pin 4
Legend:
[Pin4]
Signal level on pin 4 of the IO-Link port (DO)
1 bit
0x0
LOW
0x1
HIGH
>
Mapping: Compact Output Block
54568
IO-Link port
Register area
2 bytes/port
(n = 2)
4 bytes/port
(n = 4)
8 bytes/port
(n = 8)
16 bytes/port
(n = 16)
32 bytes/port
(n = 32)
Port X01
600
600...601
600...603
600...607
600...615
Port X02
601
602...603
604...607
608...615
616...631
Port X03
602
604...605
608...611
616...623
632...647
Port X04
603
606...607
612...615
624...631
648...663