50
Chimney cap should be used to prevent the flow into the chimney flue
repercussions of windy weather and rain.
Concrete blocks are affected by temperature changes, concrete flat roof
which is in direct contact with the air must be absolutely isolated.
An accurate and sufficient flue system for smoke extraction (a chimney
with natural traction (2 Pa - 8 Pa) that does not backfire in the event
of a power outage.)is necessary.
Necessary precautions should be taken to prevent condensate formed in
the chimney from reaching the boiler.
Clogging or closing of the flue outlet poses a great danger.
Stoves must be connected to a chimney duct which can move vertically
smoke
outside the building or its flue pipe to the highest point of the
building.
Chimney connections, if that would be considered illegal in the first
combustion
fumes can cause the wall to infiltrate the processing of
these leaks may leave traces. Leaked smoke and / or flames can cause
burns or fire because it can be
very hot.
4.5. Smoke Pipe Instructions
Horizontal chimney's duct and vertical chimney's pipe connections are very
important; therefore, it must be done carefully. Warranty of the smoke pipe
connection should be made accordingly.
The minimum safety opening surface sections should be 15%. Slope in the
horizontal section of the pipe should be 3-5%. (3-5 cm per meter). The horizontal
chimney's duct should not be longer than 2 m.
The stove chimney pipe inner diameter is 80 mm.
Horizontal chimney's duct and vertical chimney's pipe should be made of durable
materials for heat, corrosion and condensation.
Please take care of flue pipe standard’s sizes, the problems in case of using
nonstandard sizes will not be under our responsibility.