VORTEX
Refrigerant Recovery Machine
OPERATING MANUAL

Questions and Answers

  • J
    Janet MatthewsJul 27, 2025
    What to do if my Inficon VORTEX compressor won't start?
    • J
      Jeffrey NelsonJul 27, 2025
      If your Inficon Air Conditioner compressor won't start, there are several potential causes: * The power cord may not be attached: Ensure the power cord is properly connected. * There may be no voltage at the receptacle: Verify the voltage at the job site. * The circuit breaker may have opened: Identify the cause of the breaker activation, rectify the issue, and reset the breaker. * The discharge pressure might be too high, causing the HP switch to open: Reduce the pressure and rotate V2 to Purge and back to Recovery. * There could be an electronics failure in the motor: This requires factory service.
  • K
    Karen TylerAug 4, 2025
    Why does my Inficon Air Conditioner compressor start then cut out with high pressure?
    • A
      Amanda GrayAug 4, 2025
      If your Inficon Air Conditioner compressor starts but cuts out within a few minutes with a high-pressure indication, it could be due to the following reasons: * V2 is in the Purge position, activating the HP switch: Rotate V2 to the Recovery position. * V3 is not open, activating the HP switch: Rotate V3 to the open position. * The recovery tank valve is not open: Open the tank valve. * There is a blocked discharge hose: Check and clear any blockage. * There is air in the system/tank: Bleed air from the system/tank.
  • C
    Christopher PinedaAug 12, 2025
    How to prevent my Inficon Air Conditioner from overheating?
    • C
      Chase Hale IIAug 12, 2025
      To prevent your Inficon Air Conditioner from overheating, consider these factors: * Excessive head pressure due to high ambient temperature: Reduce the tank temperature. * Restricted discharge hose: Check and clear any restrictions. * Air in the recovery tank: Bleed air from the tank.
  • S
    salazarkirstenAug 18, 2025
    What to do if my Inficon Air Conditioner compressor stops intermittently?
    • D
      dominicsmithAug 19, 2025
      If your Inficon Air Conditioner's compressor stops intermittently, it could be because: * The vapor pressure of refrigerant in the tank is close to the HP trip point: Reduce the tank temperature. * The thermal overload switch in the compressor is activating: Reduce the amount of liquid being pumped and let the machine cool down before proceeding.

Summary

Preface

Safety Precautions

Specifications, Features and Warranty

Vortex Specifications

Lists the refrigerants, power, compressor, cooling, protection, pressure, temperature, case, size, and weight of the Vortex unit.

Warranty

Outlines the warranty period and conditions for the Vortex Refrigerant Recovery Machine and its compressor.

Setup and Operation

Getting Started

Details the initial steps and safety precautions for operating the Vortex unit.

Normal Recovery Operation

Explains the step-by-step procedure for normal refrigerant recovery using the Vortex machine.

PURGING the Vortex

Describes the process for purging the Vortex machine to remove residual refrigerant.

Push-Pull Operation

Details the Push-Pull method for recovering large amounts of liquid refrigerant efficiently.

Cooling The Recovery Tank

Explains how to use the Vortex to cool the recovery tank when high head pressure is encountered.

Maintenance

Introduction

Briefly introduces the importance of maintaining the Vortex for reliable service.

Troubleshooting

Service

General

Provides general guidelines and warnings regarding service and component changes for the Vortex machine.

Electrical Schematic

Inficon VORTEX Specifications

General IconGeneral
BrandInficon
ModelVORTEX
CategoryAir Conditioner
LanguageEnglish