Vortex Operating Manual
Compressor starts but
cuts out within a few
minutes — pressure
indication on HP gauge
is high
V2 is in Purge position
and HP switch activates
V3 not open and HP
switch activates
Recovery tank valve
not open
Blocked discharge
hose
Air in system/tank
Rotate V2 to Recovery
Rotate V3 to open
position
Open tank valve
Check & clear blockage
Bleed air from
system/tank
Compressor stops
intermittently
Vapor pressure of
refrigerant in tank is
close to HP trip point
Thermal overload
switch in compressor is
activating
Reduce tank
temperature
Reduce amount of
liquid being pumped and
let machine cool down
before proceeding
Unit overheats Excessive head
pressure due to:
High ambient
temperature
Restricted discharge
hose
Air in recovery tank
Reduce tank
temperature
Check & clear
restriction
Bleed air from tank
Recovery process too
slow
Head pressure too
high
System refrigerant
iced up
Compressor seals are
worn
Reduce tank
temperature or change
tanks
Throttle gauge manifold
valves and V3 to reduce
pressure differential
between LP and HP
gauges
Interrupt process to
allow ice to dissipate
Rebuild compressor
with service kit — check
with wholesaler for
assistance
PROBLEM CAUSE ACTION