EasyManua.ls Logo

Infiltrator Delta ECOPOD-N Series - Control Panel Schematics; CP2210 Control Panel Wiring Schematic; Fuse Selection Chart for CP2210

Default Icon
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Delta Treatment Systems • 9125 Comar Drive, Walker, LA 70785 • 1-800-219-9183 • www.deltatreatment.com
15
CP2210 SCHEMATIC
BY OTHERS (20 AMP MAXIMUM)
BRANCH CIRCUIT CONNECTION
EXTERNAL DISCONNECT AND
SHOR
T CIRCUIT RATING: 5KA
VOLTS - 120
PHASE/HZ - 1/60
TYPE 4X ENCLOSURE
MAX FULL LOAD AMPS - 8
CP2210/ECO/FG/UL CONTROL PANEL
SETTING HIGH LEVEL PRESSURE SWITCH
– BRING PLANT TO OPERATING WATER LEVEL
WITH COMPRESSOR TURNED ON.
– USING PROPERLY SIZED SCREWDRIVER, TURN
HIGH LEVEL ALARM ADJUSTMENT.
– SCREW CLOCKWISE UNTIL ALARM OCCURS.
THEN TURN THE SCREW COUNTERCLOCKWISE
UNTIL ALARM STOPS.
EXTERNAL WIRING
SW1
GN
H
FS1
F1
F2
R
120VAC
C
H
NG
LT1
FU1
G
N
HIGH LEVEL ALARM
FLOAT SWITCH
LOW LEVEL
HIGH LEVEL
PS
PS
SCHEMATIC DIAGRAM
HIGH LEVEL ALARM
ADJUSTMENT SCREW
GROUND
PS
F2H F1
FS1
FUSE
N
N
COMP.
TO
TB
FUSE
*TIME DELAY
HGN
120 VAC
SOURCE
COMP.
TO
G
TO COMP.
AIR LINE
CP2210/ECO/FG/UL
NTS
A
CP2210 10/03/07
11
D.WRIGHT
MOTOR FULL
LOAD CURRENT
1-4 AMPS
4-8 AMPS
12-16 AMPS
8-12 AMPS
FUSE SELECTION CHART
15 AMPS
10 AMPS
20 AMPS
5 AMPS
TYPICAL TIME DELAY
FUSE SIZE REQUIRED
CRT PART NO.
AE845-4187
AE845-4188
AE845-4180
AE845-4184
BUZZ
REVISION DESCRIPTIONREV.DATE
INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,
SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO
COMPANY CONFIDENTIAL
IT IS THE PROPERTY OF DELTA TREATMENT SYSTEMS, IT IS TO BE USED
OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF
DELTA TREATMENT SYSTEMS
.
BY
PLOT SCALE
SHEET
OF
DRAWN BY
DATE
REVDRAWING NUMBER
CP2210 SCHEMATIC

Related product manuals