EasyManuals Logo

inform PDSP 33080 User Manual

Default Icon
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
52
Free Running Frequency
[Hz]
± % 0.01
Voltage THD @ Rated
Linear Load
<%3
Nominal Apparent
Power [kVA]
10
15
20
30
40
60
80
100
120
Maximum Load P. F.
0.8
Nominal active power
[kW]
8
12
16
24
32
48
64
80
96
Nominal current [A] at
380V
15
23
30
45
61
91
121
151
182
Load Crest Factor @
Rated Power
3:1
Overload Duration
>1min @ %150 load
Efficiency (normal
operation) @rated linear
load with 0.8 PF
Up to 94% *
OUTPUT @ 1PH OUTPUT UPS’S
Performance
Classification
VFI-SS-111
-
Number of Phases
1PH+N+PE
-
Nominal Voltage [V]
220 / 230/ 240 (LINE-NEUTRAL)
-
Static
Voltage
Regulation
Normal
<%1
-
@ %100
Linear Load
Battery
Nominal Frequency [Hz]
50 / 60
-
Free Running Frequency
[Hz]
± % 0.01
-
Voltage THD @ Rated
Linear Load
<%3
-
Nominal Apparent
Power [kVA]
10
15
20
30
40
-
Maximum Load Power
Factor
0.8
-
Nominal Active Power
[kW]
8
12
16
24
32
-
Nominal current [A] at
380V
45
68
91
136
182
-
Load Crest Factor @
Rated Power
3:1
-
Overload Duration
>30sec @ %150 load
-
Efficiency (normal
operation) @rated linear
load with 0.8 PF
Up to 94%*
-
STATIC BY-PASS LINE @ 3PH OUTPUT UPS’S