EasyManua.ls Logo

INIM Electronics SmartLine036-4

INIM Electronics SmartLine036-4
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32 Installation instructions
Conventional fire detection control panel
Figure 18 - Connecting generic contacts to the detection line
The wiring diagram above illustrates the connection of a generic device (call point, switch, generic device
output) to the detection line. If the line is wired in this way, it will signal a fault when a short-circuit or
cable interruption occurs, and will generate the pre-set line signals (alarm, sprinkler, change class, etc.)
when the contact closes.
6.5.2 Connecting I/O Lines
Each zone I/O line can be wired in one of the following ways:
Figure 19 - Wiring the I/O line as an output
The diagram above illustrates a line wired as an output. The terminal will operate in the same way as an
open-collector output, that is, it will be open during standby status and close to Ground (-) in the event of
activation.
ORANGE
WHITE RED
GOLD
BLUE
GRAY BROWN
GOLD
CONTACT
LED
SIGNALLING
REL1INT
1 relay board

Table of Contents

Related product manuals