Owners Manual
Multi-Pipe VRF High Walls
VWM10H25
VWM13H25
VWM18H25
VWM24H25
Thank you for choosing our product.
For proper operation, please read and keep this manual carefully.
If you have lost the Owner’s Manual, please contact the local agent or visit
www.innovair.com or sent email to info@innovair.com for electronic version.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Question and Answer IconNeed help?

Do you have a question about the innovair VWM10H25 and is the answer not in the manual?

Overview

This document is an owner's manual for Innovair Multi-Pipe VRF High Wall air conditioning units, specifically models VWM10H25, VWM13H25, VWM18H25, and VWM24H25. The units are AHRI certified and use R410A refrigerant.

Function Description

The Innovair Multi-Pipe VRF High Wall units are designed for air conditioning, offering various operational modes including auto, cool, dry, fan, and heat. Users can control the unit via a remote controller, which allows for adjusting temperature, fan speed, and air blowing angle. The units feature an inverter technology, indicating variable compressor speed for improved efficiency and comfort.

The remote controller includes dedicated buttons for:

  • ON/OFF: To power the unit on or off.
  • MODE: To select the desired operation mode (Auto, Cool, Dry, Fan, Heat).
  • +/-: To adjust the set temperature.
  • FAN: To cycle through fan speeds (auto, low, medium, high).
  • SWING: To adjust the air blowing angle.
  • CLOCK: To set the current time.
  • TIMER ON/TIMER OFF: To schedule automatic power on or off.
  • X-FAN: To activate or deactivate the X-FAN function, which helps dry the indoor unit to prevent mold.
  • TEMP: To display indoor set temperature, indoor ambient temperature, or outdoor ambient temperature.
  • TURBO: To quickly reach the desired temperature in cool or heat mode.
  • LIGHT: To turn the display light on or off on the indoor unit.
  • SLEEP: To activate or deactivate the sleep function, which adjusts temperature for comfortable sleep.

Combination button functions include:

  • Child Lock: Pressing "+" and "-" simultaneously activates or deactivates the child lock. When active, the remote controller will blink three times without sending a signal if operated.
  • Temperature Display Switchover: Under OFF status, pressing "-" and "MODE" simultaneously switches the temperature display between Celsius (°C) and Fahrenheit (°F).

Important Technical Specifications

  • Refrigerant: R410A (R32/125: 50/50): 1975.
  • Operating Temperature Range (with electric heating): -20 ℃ to 46.1 ℃.
  • Operating Temperature Range (without electric heating): -18 ℃ to 46.1 ℃.
  • Maximum Cooling (Indoor side DB/WB): 26.7/19.4 °C.
  • Maximum Cooling (Outdoor side DB/WB): 46.1/23.9 °C.
  • Maximum Heating (Indoor side DB/WB): 26.7/- °C.
  • Maximum Heating (Outdoor side DB/WB): 23.9/18.3 °C.
  • Connection Pipe Lengths:
    • Standard: 5m, 7.5m, 8m.
    • Minimum: 3m.
    • Maximum lengths and height differences vary by cooling capacity:
      • 5000Btu/h (1465W): Max length 15m, Max height difference 5m.
      • 7000Btu/h (2051W): Max length 15m, Max height difference 5m.
      • 9000Btu/h (2637W): Max length 15m, Max height difference 5m.
      • 12000Btu/h (3516W): Max length 20m, Max height difference 10m.
      • 18000Btu/h (5274W): Max length 25m, Max height difference 10m.
      • 24000Btu/h (7032W): Max length 25m, Max height difference 10m.
      • 28000Btu/h (8204W): Max length 30m, Max height difference 10m.
      • 36000Btu/h (10548W): Max length 30m, Max height difference 20m.
      • 42000Btu/h (12306W): Max length 30m, Max height difference 20m.
      • 48000Btu/h (14064W): Max length 30m, Max height difference 20m.
  • Additional Refrigerant Charging:
    • For every additional 10m of connection pipe beyond the standard length, add 5ml of refrigerant oil for each additional 5m.
    • Additional refrigerant charging amount (g/m) varies by liquid pipe diameter and unit type (cooling only vs. cooling and heating):
      • Φ6 (1/4") liquid pipe: 15 g/m (cooling only), 20 g/m (cooling and heating).
      • Φ6 or Φ9.52 (3/8") liquid pipe: 15 g/m (cooling only), 50 g/m (cooling and heating).
      • Φ12 (1/2") liquid pipe: 30 g/m (cooling only), 120 g/m (cooling and heating).
      • Φ16 (5/8") liquid pipe: 60 g/m (cooling only), 120 g/m (cooling and heating).
      • Φ19 liquid pipe: 250 g/m (cooling only), 250 g/m (cooling and heating).
      • Φ22.2 liquid pipe: 350 g/m (cooling only), 350 g/m (cooling and heating).
  • Pipe Expanding Method (A-dimension):
    • Φ6 - 6.35 (1/4"): Max 1.3mm, Min 0.7mm.
    • Φ9.52 (3/8"): Max 1.6mm, Min 1.0mm.
    • Φ12-12.7 (1/2"): Max 1.8mm, Min 1.0mm.
    • Φ15.8-16 (5/8"): Max 2.4mm, Min 2.2mm.
  • Power Supply: Requires a qualified power supply circuit and circuit break. An all-pole disconnection switch with at least 3mm contact separation in all poles must be connected in fixed wiring. Grounding is essential.

Usage Features

  • Remote Control: The primary interface for daily operation, offering comprehensive control over the unit's functions.
  • Emergency Operation: In case of a lost or damaged remote controller, an auxiliary button on the indoor unit allows for basic ON/OFF operation in auto mode.
  • Self-Diagnosis: The unit displays error codes (e.g., E5, H6, C5, F1, F2, E6) on the indoor unit's temperature indicator to help identify malfunctions.
  • Quiet Operation: Designed to minimize noise and vibration, especially when installed correctly.
  • Anti-Cold Air Function (Heating Mode): The indoor unit delays blowing air for 1-5 minutes after starting heating to prevent cold air discharge.
  • X-FAN Function: Helps to dry the indoor unit's internal components after cooling or dry mode operation, preventing mold and odors.
  • Child Lock: Prevents unintended operation by children.
  • Temperature Display Options: Users can choose to display the set temperature, indoor ambient temperature, or outdoor ambient temperature.

Maintenance Features

  • Filter Cleaning: The air filter should be cleaned every three months, or more frequently in dusty environments. Cleaning involves opening the panel, removing the filter, washing it with water below 45°C, and drying it in a shady place. Do not touch the fins after removing the filter to avoid injury. Do not use fire or a hair dryer to dry the filter.
  • General Cleaning: The indoor unit's surface should be cleaned with a soft, dry cloth. Do not wash the air conditioner with water or spray water on the indoor unit to avoid electric shock or malfunction. Disconnect power before cleaning.
  • Pre-Season Check: Before the operating season, check for blocked air inlets/outlets, proper functioning of the air switch/plug/socket, clean filters, intact mounting brackets (indoor and outdoor), and undamaged drainage pipes.
  • Post-Season Check: After the operating season, disconnect power, clean filters and the indoor unit panel, and check mounting brackets for damage.
  • Battery Replacement: The remote controller batteries (2x AAA 1.5V) should be replaced when the display is fuzzy or blank. Ensure correct polarity.
  • Professional Maintenance: Installation and any repairs must be performed by qualified professionals. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons. Do not repair or refit the air conditioner yourself.
  • Odor Source Elimination: If odors are emitted, eliminate the source (e.g., furniture, cigarette smoke) and clean the filter.
  • Troubleshooting Guide: The manual provides a comprehensive troubleshooting guide for common issues like the unit not operating, mist emission, inability to adjust temperature, poor cooling/heating effect, odors, abnormal operation, outdoor unit vapor, "water flowing" noise, and cracking noise.

innovair VWM10H25 Specifications

General IconGeneral
Brandinnovair
ModelVWM10H25
CategoryAir Conditioner
LanguageEnglish

Related product manuals