4 Quick Steup 
 
 
4
- 29 -
Continue Para. Parameter Name Default Commissioning
H06-07 Maximum speed limit 6000
If torque control H02-00 Control mode selection 1 2
0: Speed mode 
1: Position mode 
2: Torque mode 
3: Torque mode/Speed mode 
4: Speed mode/Position mode 
5: Torque mode/Position mode 
6: Torque mode/Speed mode/Position mode
H07-00 Main torque reference A source 0
0: Digital setting (H07-03) 
1: AI1 
2: AI2
H07-19
Positive speed limit/1st speed limit 
in torque control
3000
H07-20
Negative speed limit/2nd speed limit 
in torque control
3000
Set DI if DI used H03-02 DI1 function selection 14
14: P-OT (Forward limit switch)
H03-03 DI1 logic selection 0
0: Low level valid 
1: High level valid 
2: Rising edge valid 
3: Falling edge valid 
4: Rising edge and falling edge both valid
H03-04  DI2 function selection 15
15: P-OT (Reverse limit switch)
H03-05  DI2 logic selection  0
H03-06  DI3 function selection  13
13: INHIBIT (Position reference inhibited)
H03-07  DI3 logic selection 0
H03-08  DI4 function selection  2
2: ALM-RST (Fault and warning reset)
Continue Para. Parameter Name Default Commissioning