5 Troubleshooting
 
5
- 44 -
Cause Conrming Methods Correctivee Action
2. The regenerative 
resistor is too small or 
short circuited.
If internal regenerative resistor is used 
(H02-25 = 0), check whether 
 
and D 
are connected with a cable reliably. If yes, 
measure resistance between C and D.
If external regenerative resistor is used 
(H02-25 = 1/2), measure resistance 
between 
 
and C.
For regenerative resistor specication, 
refer to Chapter 1.
If internal regenerative resistor is used and 
the resistance is 0, use external regenerative 
resistor (H02-25 = 1/2) and remove 
cable between 
 
and D. select external 
regenerative resistor of the same resistance 
and power as internal regenerative resistor.
If external regenerative resistor is used 
and the resistance is smaller than H02-21 
(allowed minimum value of regenerative 
resistor), connect a new regenerative resistor 
between 
 
and C.
Make H02-26 (power of external regenerative 
resistor) and H02-27 (resistance of external 
regenerative resistor) consistent with external 
regenerative resistor specication.
3. Motor cables are in 
poor contact.
Check whether power cables of servo 
drive and motor UVW cables are loose.
Fasten the cables that become loose or are 
disconnected.
4. Motor cables are 
grounded.
After ensuring power cables of servo drive 
and motor cables are connected securely, 
measure insulation resistance between 
UVW of servo drive and ground cable (PE) 
and check whether insulation resistance is 
MΩ-level.
Replace motor if insulation is poor.
5. Motor UVW cables 
are short circuited.
Disconnect motor cables and check 
whether motor cables (U, V, W) are short 
circuited and whether burrs exist.
Connect motor cables correctly.
6. Motor is damaged.
Disconnect motor cables and measure 
whether resistance between motor cables 
UVW is balanced.
Replace motor if resistance is unbalanced.
7. The gain setting is 
improper and motor 
oscillates
Check whether motor oscillates or 
generates a shrill noise during motor 
startup and running. You can view current 
feedback by using the drive Inovance 
servo commissioning software.
Adjust the gain.
8. Encoder cable 
is incorrectly 
wired, corrosive, or 
connected loosely.
Check whether encoder cable you use is 
standard conguration of Inovance. check 
whether cable is aging, corrosive or is 
connected loosely.
Set the S-ON signal to OFF and rotate 
motor shaft manually. Check whether 
H0B-10 (electric angle) changes as motor 
rotates.
Re-weld, fasten or replace encoder cable.
9. Servo drive faulty.
The fault persists after motor cables are 
disconnected and servo drive is powered 
on again.
Replace the servo drive.
Er.207: Shaft D/Q current overow
Cause Conrming Methods Corrective Action
1. Shaft D/Q 
current overows.
If the fault persists after you power on servo drive several times and 
restore default setting, it indicates that the servo drive is faulty.
Replace the servo 
drive.