Communication Parameters
‑19‑
4 Communication Parameters
4.1 Communication Card Type Setting for the AC Drive
Communication Card Type Setting for the MD520 Series AC Drive
After powering on the AC drive, set FD‑00 to 9 and FD‑01 to 3 to enable
communication between the MD500‑EM1 card and the AC drive.
Parameter Name
Value Range
Value
Description
FD‑00
Baud rate
Ones position
0: 300 bps
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
8: 57600 bps
9: 115200 bps
Tens position:
Reserved
Hundreds
position:
Reserved
Thousands
position:
CANlink baud
rate
0: 20
1: 50
2: 100
3: 125
4: 250
5: 500
6: 1 Mbps
Ones position: 9
Sets the data
transfer rate
between the
communication
extension card
and the AC
drive.
FD‑01
Modbus data
format
0: No check (8‑
N‑2)
1: Even parity
check (8‑E‑1)
2: Odd parity
check (8‑O‑1)
3: No check (8‑
N‑1)
3
Sets the format
of Modbus data
transmitted
between the
communication
extension card
and the AC
drive.