Communication Parameters
20
Communication Card Type Setting for the MD500-PLUS Series AC Drive
After powering on the AC drive, set FD‑00 to 9 and FD‑01 to 3 to enable
communication between the MD500‑EM1 card and the AC drive.
Parameter Name
Value Range
Value
Description
FD‑00
Baud rate
0: 300 bps
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
8: 57600 bps
9: 115200 bps
9
Sets the data
transfer rate
between the
communication
extension card
and the AC
drive.
FD‑01
Modbus data
format
0: No check (8‑
N‑2)
1: Even parity
check (8‑E‑1)
2: Odd parity
check (8‑O‑1)
3: No check (8‑
N‑1)
3
Sets the format
of Modbus data
transmitted
between the
communication
extension card
and the AC
drive.
4.2 IP Address Setting of MD500-EM1 Card
The following table describes the IP settings of the communication card.
Parameter Name
Value Range Description
FD‑37
DHCP enable
0: Disable DHCP
1: Enable DHCP
Sets the DHCP
function of the card.
Once the DHCP
function is enabled,
the manual IP settings
do not take effect.
FD‑38‑FD‑41
IP address
0 to 255
Sets the IP address of
the card.
FD‑42‑FD‑45
Subnet mask
0 to 255
Sets the subnet mask
of the card.
FD‑46‑FD‑49
Gateway
0 to 255
Sets the gateway of
the card.
The IP address may be either static or dynamic one. You can choose the IP address
allocation mode by setting FD‑37. You can set the static IP address using parameters
FD‑37 to FD‑49. For example, if you want to configure static IP address to 192.168.0.6,
subnet mask to 255.255.255.0 and gateway to 192.168.0.1, use the parameter settings
in the following table.