152
After the command insert the port number with 4 digits.
Note: This eld denes the port to which the center will connect, factory default :
9009
. Intelbras IP Receiver software must be congured for the same port.
Important: you must not use the same port from another manufacturer for this
communication, because there is the possibility of conict.
» Program target domain name (DNS)
If you don't want to use DNS, go to the next command, otherwise, type:
Enter + 803 + D + Enter
, D = 1 or 2 (DNS 1 or DNS 2)
After the command, type the DNS domain name and press the
Enter
key to conrm.
» Program monitoring options via IP
Enter + 830 + Enter
After the command, using the keys on the keyboard, enable the desired option
from 1 to 4, where:
» 1: enables the sending of events to the monitoring company 1
» 2: enables the sending of events to the monitoring company 2
» 3: enables the domain name (DNS) of the monitoring company 1
» 4: enables the domain name (DNS) of the monitoring company 2 and press the
Enter
key to conrm.
» Program DHCP
If you do not have a DHCP server or do not want to use this option, perform the
next step, otherwise, type the following command and also the next ones.
Enter + 831 + Enter
After the command, using the keys on the keyboard, enable option
1
(marking 1)
and press the
Enter
key to conrm.
» IP address of the alarm center
Enter + 8120 + Enter
After the command, enter the IP address for the alarm center.
Note: You can only edit/enter the address manually if the
DHCP
function is
disabled, otherwise only the IP address of the alarm center will be displayed.
» Programming the network mask
Enter + 8130 + Enter
After the command, enter the network mask number and press the
Enter
key to
conrm.