Chapter 5: Menu reference 
234  Advisor Advanced ATSx500A(-IP) Installation and Programming Manual 
8.1.2.2.1 Internal siren 
8.1.2.2.2 External siren 
Enter the delay time for the internal / external siren. The input format is 
hh:mm’ss. The allowed range is from 00:00’00 to 06:00’00. 
Caution: In an unset condition the internal siren delay is ignored and the siren 
activates instantly. 
8.1.3 System misc opts 
The System misc options menu allows you to set up all system programmable 
timers.  
8.1.3.1 Armed display 
 
The Armed display delay is a delay before the armed display is activated on the 
keypad LCD when it enters the idle state. The input format is mm’ss. The allowed 
range is from 00’00 to 10’00. 
8.1.3.2 Card and PIN 
 
The Card and PIN menu lets you set the maximum delay time between 
presenting the card and entering the PIN (default is 10 seconds). The input 
format is mm’ss. The allowed range is from 00’00 to 05’00. 
8.1.3.3 Walk test time 
 
The Walk test time menu option defines the maximum time for the walk test (0 to 
30 minutes). A value of 00’00 means no limitation, in this case the walk test is 
ended only by the user, or when completed successfully. For more information, 
see “1.2.5 Walk test” on page 130. 
8.1.3.4 Mains reporting delay 
 
4 Mains rep dly 
 >00:00’00< 
The Mains reporting delay option defines the delay time (0 to 4 hours) before a 
mains fail is reported to the central station. Enter a value of “0” for immediate 
reporting.