ET270 SERIES
INCLUDING MODELS:
ET279C (SPST each output)
120V Supply
Electronic 7 - Day Time Switches
With 2 Independent Outputs and
Battery Powered Clock Operation
OWNER/INSTALLER INSTRUCTION MANUAL
ATTENTION: READ CAREFULLY BEFORE ATTEMPTING TO INSTALL YOUR INTERMATIC
TIME SWITCH. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE! RETAIN FOR FUTURE REFERENCE.
Specifications
CLOCK VOLTAGE: 120 V.A.C., 60 Hz.
POWER CONSUMPTION: 5.0 Watts Max.
CONTACT CONFIGURATION: SPST for output 1 and 2
SWITCH RATING: (Per Pole)
30 Amps Inductive/Resistive, 24/120/240 V.A.C., 60 Hz.
20 Amps Resistive - 28 V.D.C.,
1 H.P. 120 V.A.C., 60 Hz.
2 H.P. 240 V.A.C., 60 Hz.
5 Amps Tungsten, 120/240 V.A.C., 60 Hz.
20 Amps Ballast 277 V.A.C., 60 Hz.
SET POINTS (EVENTS): 20 total for both outputs combined in
any combination (10 ON/10 OFF or any combination or 20
momentary pulse operations) daily.
Up to 140 (70 ON/70 OFF or any combination or 140 pulse
operations) weekly.
BATTERY POWERED CLOCK OPERATION: 3 Years minimum
(AA industrial grade alkaline supplied with time switch)
MIN. “ON” or “OFF” TIME: 1 minute.
MAX. “ON” or “OFF” TIME: 6 days 23 hours 59 minutes.
SHIPPING WEIGHT: 2..5 Lbs. (1.1 Kg)
CASE: Drawn steel; 7-3/4” (19.7 cm) high, 5” (12.7 cm)
wide, 3” (7.6 cm) deep; gray finish w/lockable spring hasp.
KNOCKOUTS: Combination 1/2 - 3/4” (one on back and
each side, two on bottom).
WIRE SIZE: AWG #10 through #18.
General Safety Information
WARNING: Disconnect all power before installing or
servicing this time switch or its connected loads.
1.Follow all local electrical and safety codes, National
Electric Code (NEC), as well as Occupational Safety and
Health Act (OSHA).
2. If the power disconnect point is out of sight, lock it in the “OFF”
position and tag it to prevent unexpected application of power.
3. This time switch case must be grounded.
4. Do not exceed the maximum current carrying capacity of this
time switch.
5. Always replace the plastic insulator covering the terminal
before turning power “ON”.
Installation
WARNING: DISCONNECT THE POWER TO THE TIME
SWITCH AND THE LOADS BEFORE INSTALLING THIS TIME
SWITCH.
1. Mount the time switch in the desired location using the three
mounting holes which are provided. Mount the time switch at
eye level, if possible, providing sufficient room to the left of the
AM ON
5:20
Description
The Intermatic Electronic 7-Day Time Switch automatically
switches 2 loads independently according to a preset weekly
schedule with to-the-minute accuracy. This time switch is
designed to directly switch resistive or inductive loads up to 30
amps at 24, 120 or 240 volts and to switch tungsten or ballast
loads up to the time switch rating. For use as a control timer in
applications requiring 7-day load control such as lighting,
heating, air conditioning systems, pumps, etcetera. Up to 20 (10
ON/10 OFF or any combination or 20 momentary pulse
operating) can be preset. These set points can be programmed
for any or all 7 days to provide for up to 140 set points or pulse
operations each week. Independent 2 load 7 day programming
provides complete flexibility for applications where load switching
differs each day of the week. The program can be overridden by
selecting the MANUAL position.

Questions and Answers

  • S
    sperezJul 30, 2025
    What to do if the Intermatic Switch load doesn't switch at the programmed time?
    • P
      Phyllis SanchezJul 30, 2025
      If the Intermatic Switch doesn't switch at the programmed time, ensure the MANUAL/AUTO selector is in the AUTO position. Review the program settings by placing the OUTPUT Selector in the OUTPUT 1 or OUTPUT 2 mode and pressing the ENTER button to check all twenty settings. Also, confirm that power is supplied to the line terminals to power the load. Remember that the output contacts are isolated from the timer power, allowing the timer to switch various loads from 24 volts through 277 volts.
  • A
    Andrew LeAug 5, 2025
    How to fix scrambled times on Intermatic Switch display?
    • L
      Larry LucasAug 6, 2025
      If your Intermatic Switch display shows scrambled or erratic times: * Try resetting the time switch by pressing and holding the recessed reset switch for about 5 seconds. * Consider installing surge suppressors (metal oxide varistors- MOVS) across terminals 3/4 & 5/6 to help reduce electrical noise generated at the switching contacts, although electrical noise interference is highly unlikely since the electronic circuitry and the power supply are completely isolated.
  • C
    Cheryl HinesAug 11, 2025
    Why does my Intermatic ET279C have no display?
    • J
      Jason WilliamsAug 11, 2025
      If the Intermatic Switch has no display, the battery may not be properly installed or could be defective. Check the battery and replace it if necessary.
  • M
    Monique ScottAug 18, 2025
    What to do if Intermatic ET279C Switch displays “Err 1”, “Err 2”, or “Err 3” message?
    • S
      Susan LiuAug 18, 2025
      If the Intermatic Switch displays an “Err 1”, “Err 2”, or “Err 3” message, it indicates an issue with the slide switch. Reposition the slide switch into its detent position or try to "wiggle" it until the display corrects itself. If the display still shows the error, return the switch to the factory for service.
  • F
    Francisco JacksonAug 25, 2025
    What does “L-bA” mean on Intermatic ET279C display?
    • J
      joshuaburkeAug 25, 2025
      If the Intermatic Switch display shows “L-bA”, replace the battery within 30 days.

Summary

Specifications

General Safety Information

Important Installation Warning

Crucial advisory to read all instructions carefully before installation to prevent injury or damage.

Adherence to Codes

Follow all local electrical and safety codes, including NEC and OSHA regulations.

Power Disconnect Safety

Lock power disconnect in 'OFF' position and tag it to prevent unexpected power application.

Grounding Requirement

Ensure the time switch case is properly grounded for safe operation.

Current Capacity Limit

Do not exceed the maximum current carrying capacity of the time switch.

Terminal Insulator

Always replace the plastic insulator covering terminals before turning power ON.

Installation Steps

Programming Operations

Troubleshooting Guide

Intermatic ET279C Specifications