3.6 AJOUT DE SECTION
Ajoutez des sections de cheminée, selon les instructions
d’installation des manufacturiers. La cheminée doit dé-
passer le toit d’au moins 3’ (0,9m) de son point de con-
tact avec la toiture, et 2’ (0,6m) de tout mur, toit ou édi-
fice se trouvant à l’intérieur d’une distance horizontale
de 10’ (3,1 m).
3.6 SECTIONS
Add chimney sections, according to the manufacturers
installation instructions. The chimney must extend at
least, 3 feet (1m) above its point of contact with the roof
and at least 24 inches (61cm) higher than any wall, roof,
building or obstacle within 10 feet (3m) horizontally.