Note: For the 2-wire running mode, when
FWD/REV terminal is valid, the VFD stop
because of the stopping command from other
sources, even the control terminal FWD/REV
keeps valid; the VFD won't work when the
stopping command is canceled. Only when
FWD/REV is re-launched, the VFD can start
again. For example, the valid STOP/RST stop
when PLC signal cycles stop, fixed-length stop
and terminal control (see P07.04).
The function code defines the corresponding
delay time of electrical level of the programmable
terminals from switching on to switching off.