Chapter 1. Product Overview
Shenzhen INVT Network Technology Co., Ltd. 7
1.6 Operating environment requirements
The operating environment of VCP series air-cooled outdoor units should meet the
requirements of Table 1-5.
Table 1-5 Operating environment requirements
Equivalent distance between indoor unit and outdoor unit in standard
configuration is 30m, height difference ΔH: -5m ≤ ΔH ≤ 20m; installation
method: horizontal or vertical installation.
Outdoor:-15℃~+45℃,-34℃~-15℃Additional low temperature component
are required.
Outdoor unit:5%RH~95%RH(No condensation)。
No more than 1000m, and deratied is required for more than 1000m.
The whole machine is IPX5.
Notes.
"ΔH": outdoor unit is higher than indoor unit for positive drop, and vice versa for negative drop.
Notes
1) When the equivalent distance between indoor unit and outdoor unit in standard
configuration is within 30m, please refer to the specific requirements for refrigerant and
connection pipe equivalent length in the user manual of indoor unit.
2) When the equivalent distance between indoor unit and outdoor unit in standard
configuration exceeds 30m, please consult the relevant technical department.