Chapter 2. Installation of outdoor unit
Shenzhen INVT Network Technology Co., Ltd. 11
Figure 2-3 Dimensional drawing of low temperature component mounting base (unit: mm)
Table 2-3 Mounting hole size (unit: mm)
2.2.3 Installation space
There should be sufficient installation and maintenance space around the outdoor unit
installation location.
Space requirements
1) Outdoor units require a maintenance space of at least 600mm in front and behind.
2) No obstruction within at least 3000mm of the outdoor unit outlet refer to Figure 2-4,
Figure 2-5.
3) When an outdoor unit is placed on top of another outdoor unit, the above outdoor unit
must be installed on the bracket and a cushion must be added between the unit and the
bracket to play the role of vibration isolation. The correct operation is shown in Figure
2-6.
4) Please refer to Figure 2-7 for the schematic diagram of low temperature component
installation.
Figure 2-4 Horizontal installation space requirements (unit: mm)