IPS home inverter manual
www.ips-ups.eu 4.09.2017
info@ips-ups.eu IPS-home-inverter-manual_ENG-R1
12
11
INLS: Inverter no-load shutdown
function
Note: If select Y, check whether the
configured load rate in Inverter
shutdown load rate is correct or not,
if not, change it. (option)
N
Y / N
12
INLS: Setting of the load rate of UPS
auto-shutdown, The load rate of
shutdown needed on the scene shall
prevail during application. (Shall be taken
as valid only when DC supply power)
(option)
3 %
3 % ~ 50 %
13
INLS: Setting of the delay time of
UPS auto-shutdown, When load
setting value, the system will shut
down after the configured time.
(Shall be taken as valid only in
battery mode) (option)
1 min
1 ~ 99 min
14
ACAU: AC self-starting function
(option)
Y
Y / N
15
DCAU: DC auto restart function
Note: If select Y, check whether
the configured time in DC auto
restart time is correct or not, if not,
change it. (option)
N
Y / N
16
T: DC auto restart time (option)
1H
0.5H ~ 8.0H
17
ITR: Input voltage display setting ,
displays the current rated voltage of
the system; If select “100 /…/ 240”,
the input voltage displays “100V /…/
240V”, the transformer variable is the
configured voltage value: rated
voltage value. (option)
OFF
200 - 240V
UPS: OFF /
100 / 110 /
115 / 120;
100 - 120V
UPS: OFF /
200 / 220 /
230 / 240
18
OTR: Output voltage display setting,
displays the current rated voltage of
the system; If select “100 /…/ 240”,
the output voltage displays “100
V/…/240 V”, the transformer variable
is the configured voltage value: rated
voltage value. (option)
OFF
200 - 240V
UPS: OFF /
100 / 110 /
115 / 120;
100 - 120V
UPS: OFF /
200 / 220 /
230 / 240
19
SAVE: Save and Exit
Y / N