Set to System Address A (S1 = OFF, S2 = OFF)
Set to Tool Address A8 (S4 = OFF, S5 = OFF, S6 = OFF)
Set Delay Time to 5sec (S3 = ON)
Test it manually - Open / Close Gate A8
Set Delay Time to your preference
Set Mode to Auto - Ready to work with other iVAC modules
Set to System Address A (S1 = OFF, S2 = OFF)
Set to Tool Address A8 (S4 = OFF, S5 = OFF, S6 = OFF)
Test it manually - ON / OFF to control Gate A8 and Switch A
Test Auto Mode with tool A4 to control Gate A8 and Switch A
Set to System Address A (S1 = OFF, S2 = OFF)
Set to Tool Address A8 (S3 = OFF, S4 = OFF, S5 = OFF)
Test it manually - ON / OFF to control Gate A8 and Switch A
Set to System Address A (S1 = OFF, S2 = OFF)
Set to Tool Address A1 (S4 = ON, S5 = OFF, S6 = OFF)
Set Delay Time to 5sec (S3 = ON)
Test it manually - ON / OFF - Open / Close Gate A1
Turn on any of A2-A8 to test A1 close
Turn off all of A2-A8 to test A1 open
Set to System Address A (S1 = OFF, S2 = OFF)
Set to Tool Address A1 (S4 = ON, S5 = OFF, S6 = OFF)
Open any of A2-A8 to close A1
Test it manually - ON / OFF to control Gate A1 and Switch A
Turn on Tool A1 to open Gate A1
Turn off Tool A1 to Close Gate A1
Set to System Address A (S1 = OFF, S2 = OFF)
Set to Tool Address A1 (S3 = ON, S4 = OFF, S5 = OFF)
Open any of A2-A8 to close A1
Test it manually - ON / OFF to control Gate A1 and Switch A