LOW PRESSURE SWITCH ALARM
To reset the alarm:
Press “Ackn.”
ALARM (LP)
Low pressure switch
020301 15:10:18
Info Ackn.
Probable causes and actions:
Air in the heating system.
Action: Check the expansion vessel and fill if required. If air is heard continuously in the system,
contact the installer.
Heat transfer pump has stopped or is set at too low a speed.
Action: Check the pump has not stopped or is set at the wrong speed.
Particle filter on the cold side is clogged.
Action: Check the particle filter and clean if necessary.
Not enough refrigerant in the circuit.
Action:Check that bubbles do not appear continuously in the sight glass. Contact the installer.
Not enough antifreeze in the heat transfer circuit creating ice in the heat exchanger.
Action: Contact the installer.
Expansion valve faulty (alarms occur at long intervals, about every three or four weeks).
Action: Contact the installer.
HIGH PRESSURE SWITCH ALARM
To reset the alarm:
Press “Ackn.”
ALARM (HP)
High press. switch
020301 15:10:18
Info Ackn.
Probable causes and actions:
Air in the heating system.
Action: Check the system and vent the radiators if necessary.
Not enough flow over the heat pump.
Action:Check that the circulation pump has not stopped and that a valve in the system is not closed.
Particle filter on the hot side is clogged.
Action: Check the particle filter and clean if necessary.
Heat transfer fluid circuit over-filled.
Action: Contact the installer.
Drying filter clogged.
Action: Contact the installer.