ALARM, HIGH RETURN TO THE HEAT PUMP
To reset the alarm: The alarm resets itself and the heat
pump starts automatically when the temperature has
dropped.
ALARM (GT9)
High return HP
020301 15:10:18
Info Ackn.
Probable causes and actions:
The heat pump has a sensor that stops the heat pump for safety reasons when the return temperature is
too high, about 48°C
The temp. incr/decr dial is set so high that the heating system return temperature is too high.
Action:Reduce the temp. setting.
The hot water temperature is set too high.
Action: Contact the installer.
The radiator valves or the underfloor heating system are closed.
Action:Open the valves.
The flow across the heat pump is greater than the flow in the heating system.
Action: Reduce the speed of the heat pump circulation pump or increase the speed of the main pump
in the heating system. Contact the installer.
SENSOR ALARM
To reset the alarm: The alarm resets itself and the heat
pump starts automatically when the fault has been cor-
rected.
ALARM (GT1)
Sensor return rad.
020301 15:10:18
Info Ackn.
Probable causes and actions:
Alarm if a sensor fault can be indicated for all sensors that are connected to the heat pump. The exam-
ple shows the alarm for the Return radiator, GT1 sensor. The principle is the same for all sensor alarms.
Short circuit or broken cable to sensor.
Action: If you have an instrument that can measure resistance, you can check the resistance of the
circuit and compare with the table for sensors in Technical spec. Or contact your installer.
Faulty sensor.
Action: Contact the installer.
Faulty connection.
Action: Contact the installer.
Temporary fault.
Action:Wait and see.
HEAT TRANSFER FLUID SYSTEM OUT MAX
ALARM
To reset the alarm: The alarm resets itself and the heat
pump starts automatically when the temperature has
dropped.
ALARM (GT8)
HTF out max
020301 15:10:18
Info Ackn.
Probable causes and actions:
The heat pump has a sensor that stops the pump for safety reasons when the outgoing temperature is
too high at around 75°C.
Not enough flow over the heat pump
Action:Check that the circulation pump has not stopped and that a valve in the system is not closed.
Particle filter on the hot side is clogged.
Action: Check the particle filter and clean if necessary.