6 november 2015, 10:05 - Jaga N.V.
Jaga Room Thermostat JRT-100 setup / user
Programmable Time settings:
press the “M” button for 5 seconds to enter “clock setting” (88:88) and “day setting”
enter 5+1+1 programmable mode
press “+” and “-“ to set the thermostat “on/off time”
next mode setting: toggle trough the menu with the “M” button. Activate the programmed time: press and hold the “ “ button for 5
seconds.
To deactivate the programmed time: press and hold the “ button for 5 seconds
Week
1st time zone 2nd time zone
Turn on Turn Off Turn on Turn Off
Icons
1
2 3 4
1
2
3 4
1 2
3
4
1 2 3
4
12345 (Monday~Friday) 8:30 12:00 14:00 18:00
6(Sat.) 9:00 12:00 15:00 18:00
7(Sun.) 9:00 12:00 15:00 18:00
Control panel:
Programming & week / day Clock
Room temperature
Set temperature
Room temperature
Set temperature
Heating / Cooling / Auto Select
& Programmable setting
Fan speed:
Low
Mid
High
Auto fan
Temperature / Parameter setting - / +
Fan speed Mode On / Off
Heating
Cooling
Heating & Cooling (4-pipe)
Parameter settings
set Power Off, bij pressing the “ ” button
to access the MENU , press and hold “M” and “+” buttons simultaneously for 10 seconds until “01” displays. Press “+” and “-“ to change
the settings.
toggle trough the menu with the “M” button
Menu Description Range
01 Temp. Offset -8 °C ~8°C
04 Set Point High Limit 10 °C ~4C
05 Set Point Low Limit 10 °C ~4C
06 LCD temperature display Room/ Room Set / Set (default Room)
07 Temperature setting / Program 10 °C ~20°C
11 Dead Band 0°C~3°C (default 0,5°C)
12 NTC select Room: internal sensor / Floor: optional external room temperature sensor
13 2-pipes/4-pipes select 2V/4V (default 4V)
14 (0-10V) select dead band or not 0: with dead band 1: without dead band (default 0)
15 Reboot memory OF/LA
19 Restore Re
20 Software version