Page: 6
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 2 Cylinder Assembly
2.3.2 Mv Series Valve Features
(See Figure 2.3.2)
e Mv Series cylinder valve has six key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge Connection: A female connection serves as the attachment point for the pressure
gauge. It is fitted with a Schrader valve to allow the removal of the gauge while the cylinder is
pressurized.
3. Low-Pressure Supervisory Switch Connection: A female connection serves as the attachment point
for the low-pressure supervisory switch. A Schrader valve allows for the removal of the pressure switch
while the cylinder is pressurized.
4. Rupture Disc: A frangible rupture disc is fitted to the valve body opposite the discharge outlet. It
functions as an emergency relief device in the event of excessive internal pressure within the cylinder.
Its rupture point is between 850 psi (58.6 bar) and 1000 psi (68.9 bar). e rupture disc shall not be
removed while the cylinder is under pressure.
5. Discharge Outlet: A 2 in (50 mm) grooved connection serves as the attachment point for discharge
piping.
6. Pilot Actuation Port: A 1/4 in (8 mm) NPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s)
. is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.2 Mv Cylinder Valve Assembly
Pressure Gauge
Connection (2)
Grooved
Coupling (Part
of Anti-Recoil
Safety Device)
Low-Pressure
Supervisory Switch
Connection (3)
Pilot Actuation
Port (6)
Safety
Cap
Rupture
Disc (4)
Valve Actuation
Connection (1)
Discharge
Outlet (5)
Pressure Gauge
Connection (2)
Ensure that the pilot actuation port pipe plug is in place before attempting to ll the cylinder assembly. Failure to
do so may result in agent leaking out of the pilot actuation port during the ll procedure.